[[Tasks at Site]] -Arrived at 11:20 and left 14:30 (Shimajiri, Inoue and Kobiki-sa) and 16:10 (Vasquez and Komatsu people). -We meet with Joaquin Collao at the site, he meets few minutes with Komatsu people. -With Shimajiri-san check the control room, the computers and preview steps for next restart the site. -I teached to Shimajiri-san about new generators. -Komatsu maintenance: --Komatsu people continuum working in the 65098 generator: ---First they tried start the generator changing the "purger of the fuel", but not work (check photo in Picasa). ---Second they tried start the generator removing the air filters, but not work (check photo in Picasa). ---Third they tried start the generator making a bypass to fuel filter, but not work (check photo in Picasa). ---After they check the injectors, but not work (check photo in Picasa). ---They use the satellite phone for contact Komatsu Antofagasta (Patricio Diaz), they decided check the solenoid one more time. They finally think that the problem is that they need regular synchronization of governor linkage fuel. ---They decide comeback tomorrow. -Check the generator: --Large fuel tank, Closed South 14.900L, Open North 11.600L. --65098 (OFF) ---KW (0), Charge control (Charger), Fuel (75%), Fuel Valve (open), racor filter (close). --65099 (ON, for test all tonight) ---RPM (1800), Hz (60), V L-N (129), V L-L (221), temp °C (25), Time (2458.04 hrs), KW (0), Charge control (Charger), Fuel (60%), Fuel Valve (open), racor filter (close).