Tasks at Site
- Arrived at 11:15 and left 16:00.
- We checked the 65099 generator, it's Ok.
- 65099 (ON, for test all tonight)
- RPM (1797), Hz (60), V L-N (125), V L-L (216), Oil Pres Psi ( 28), temp °C (77), Time (2477.25 hrs), KW (0), Charge control (Charger), Fuel (60%), Fuel Valve (open), racor filter (close).
- We stop the 65099 generator.
- Komatsu maintenance:
- Komatsu people continuum working in the 65098 generator:
- With Shimajiri-san and Komatsu technical tried the procedure sent by Iwashita and Oshima-san, step by step, but not working.
- The Komatsu technical regaled the solenoid of control and dipstick of governor, this task took close 3 hours (the steps was).
- Check the generator:
- Large fuel tank, Closed South 14.900L, Open North 11.500L.
- 65098 (ON)
- RPM (1795), Hz (59.8), V L-N (128), V L-L (222), Oil Pres Psi (0), temp °C (72), Time (1307.09 hrs), KW (0), Charge control (Charger), Fuel (70%), Fuel Valve (open), racor filter (close).
- We stop the 65098 generator.