Tasks at Site
- Arrived at 10:40 and left 13:20 (ASTE Site).
- Tamura-san makes backup data.
- Tamura-san tuning the UPS in control room.
- Tamura-san and I prepared the grease for the EL, AZ antenna system.
- I coordinate the Juan Donoso works at the site.
- We had a problem in the Control room:
- Usually the voltage in the Control room is between 105 [V] and 110 [V].
- When we make a Switch Genset, the voltage in the control room usually is a pick of 120 [V] for 1 or 2 seconds.
- Today we had a pick of 120 [V] for 10 minutes, after comeback between 105 [V] and 110 [V].
- For this reason the UPS was automatically disconnect for 10 minutes of the generator energy and give energy to the PC from the internal battery.
- Check the generator #7001 and #7002.
- #7001 12938hrs. #7002 10832hrs.
- Switch Genset, #7001 --> #7002.
- South:closed 9500L, North:open 8100L.