[[Tasks at Site]] -Arrived at 11:10 and left 18:30 (ASTE Site). -We meet with Joaquin Collao and Nicolas Silva at the site, they meet few minutes with Komatsu people. -I check the roof in the generator room, I found some issues, I will try to repair next tomorrow (Check photos in Picasa). -Check the generator: --Large fuel tank, Closed South 14.900L, Open North 11.700L. --65098 (OFF) ---KW (0), Charge control (Charger), Fuel (75%), Fuel Valve (open), racor filter (close). --65099 (OFF) ---KW (0), Charge control (Charger), Fuel (75%), Fuel Valve (open), racor filter (close). -Komatsu maintenance: --Komatsu people made regular maintenance to 65099 generator, the 65099 it's Ok. --I down the big switches (65098 and 65099) in the gray box in the generator room (Check photo in Picasa). --Komatsu people and me start the 65099 generator. --65099 (check parameters). ---RPM (1797), Hz (59.9), V L-N (129), V L-L (223), temp °C (79), Time (2456.31 hrs), KW (0), Charge control (Charger), Fuel (75%), Fuel Valve (open), racor filter (close). --Komatsu people and me check the status in the 65099 generator. ---Check the voltage in the left side box and we have ~220V fase-fase. ---We stop the 65099 generator. ---I up the big switch (65099) in the gray box in the generator room (Check photo in Picasa). ---Komatsu people and me start the 65099 generator. ---Check the voltage in the generator room, we have light, the 65099 and the electrical network is ok. ---We stop the 65099 generator. ---I down the big switch (65099) in the gray box in the generator room (Check photo in Picasa). --Komatsu people made regular maintenance to 65098 generator. ---Komatsu people and me try to start the 65098 generator, but not work. ---They check the generator (Check photos in Picasa), I told them about no change the long in the part indicated by Iwashita-san, they check the solenoid but discovered that this is not the problem. ---They decide comeback tomorrow.