Komatsu people made regular maintenance to 65099 generator, the 65099 it's Ok.
I down the big switches (65098 and 65099) in the gray box in the generator room (Check photo in Picasa).
Komatsu people and me start the 65099 generator.
65099 (check parameters).
RPM (1797), Hz (59.9), V L-N (129), V L-L (223), temp °C (79), Time (2456.31 hrs), KW (0), Charge control (Charger), Fuel (75%), Fuel Valve (open), racor filter (close).
Komatsu people and me check the status in the 65099 generator.
Check the voltage in the left side box and we have ~220V fase-fase.
We stop the 65099 generator.
I up the big switch (65099) in the gray box in the generator room (Check photo in Picasa).
Komatsu people and me start the 65099 generator.
Check the voltage in the generator room, we have light, the 65099 and the electrical network is ok.
We stop the 65099 generator.
I down the big switch (65099) in the gray box in the generator room (Check photo in Picasa).
Komatsu people made regular maintenance to 65098 generator.
Komatsu people and me try to start the 65098 generator, but not work.
They check the generator (Check photos in Picasa), I told them about no change the long in the part indicated by Iwashita-san, they check the solenoid but discovered that this is not the problem.